layer hidden off the screen

  


Atlantis II Fire Safety Systems Section


 1.Water Systems
       1.Water Pumps
            1.Water fire fighting systems are to be capable of maintaining a continuous supply in the event of damage to water piping. Piping is to be arranged so that the supply of water could be from two different sources. Isolation valves are to be provided such that damage to any part of the system would result in the loss in use of the least possible number of hydrants, water spray branches, or foam water supplies. In most facility arrangements this will require a loop type fire main. Connections of the primary and standby pump supplies are to be as remote from each other as possible.
            2.Materials rendered ineffective by heat are not to be used in firewater piping systems.
            3.Resilient seated valves may be considered for use in firewater systems, provided the proposed valves are capable of passing an appropriate fire test (e.g. UK/DOT Appendix D Fire Test Requirements to Fire Mains and Fittings ). Additionally, the valves must be capable of being effectively closed even with the resilient seat damaged or destroyed, such that leakage through the closed valve is insignificant. The leakage rate at the firewater pressure through the closed damaged-seated valves still permits the firewater to deliver at least two jets of water at the required pressure.
            4.Non-metallic expansion joints may be considered for use in firewater systems, provided the proposed joints are capable of passing a recognized fire test such as the UK/DOT Appendix D.
            5.All plastic piping materials are to meet Appendix 1 of this Guide. Generally, plastic (GRP/FRP) materials used in firewater systems are to pass Level 1 fire endurance test. However, a plastic piping material that passes Level 3 fire endurance requirements in lieu of Level 1 requirements may be considered.
            6.The firewater distribution system may be maintained in a charged or dry condition. Where a system is maintained dry, relief devices and additional pipe bracing is to be considered to prevent damage to the piping system due to water hammer when the system is charged. When plastic pipe that passes only Level 3 fire endurance test is used, the firewater system design is to be pressurized (wet main) and permanently in a charged condition.
            7.The distribution system is to be maintained such that internal and external corrosion of the piping is minimized. In areas where the system is subject to freezing, steps are to be taken to prevent freezing. For instance, drains, circulation loops or other means may be provided for cold water protection. If drains are provided, they are to be located at the lowest points in the system.
            8.There are to be at least two independently driven and self-priming fire pumps. The fire pumps, together with their respective source of power, fuel supply, electric cables, lighting, ventilation, piping and control valves, are to be located such that a fire in any one location will not render both fire pumps inoperable. One of the two pumps is to be designated as the primary fire pump, and the other as the standby fire pump. At least one of the pumps is to be diesel engine driven, unless the emergency power supply can supply the load for an electric motor driven pump. Fire pump installations are to be in accordance with NFPA 20, or an equivalent standard.
            9.The primary and standby fire pumps are each to be capable of supplying the maximum probable water demand for the facility. The maximum probable water demand is the total water requirement for protection of the largest single fire area plus two jets of firewater at a pressure of at least 5.3 kg/cm 2 (75 psi). Multiple pump installations will be considered in lieu of a single primary and/or standby pump installation, provided they are arranged in such a manner that a fire in one area would not reduce the available supply of firewater required to handle that fire, or such that if the largest pump is out of service for maintenance, the available supply of water would not be reduced below the maximum probable water demand. A means is to be provided for periodic testing of each fire pump.
           10.Pump(s) with sufficient capacity for process water spray systems is (are) to be provided with automatic starting. In addition to the pump automatic starting requirement, pump driver starters are to be provided with means for local and remote operation from a permanently manned station or a fire control station. Pump discharge control valves, used to separate the section of the firewater service system and the fire pump(s), are to be fitted in an easily accessible location outside of the pump space. Diesel-driven fire pumps may be provided with electrical or pneumatic starting and control systems. Diesel drives using electrical starting and control systems are to be maintained in a weather-protected enclosure. Alternative means of protecting electrical starting and control system will be considered.
           11.Firewater stations are to be located so that each station will be readily accessible in the event of a fire. All materials that comprise the firewater station and the access to firewater stations are to be of steel or equivalent material which would not be rendered ineffective by heat. Fiber Reinforced Plastic (FRP) grating may be used if the layout is designed in accordance with Appendix 3, and provided that the FRP grating is approved as meeting the applicable criteria defined in same.
           12.The firewater stations are also to be arranged to provide protection against fire damage or mechanical damage, operation free from interference by other emergency activities, and effective coordination with other stations.
           13.Monitors are to be sized for a minimum flow of 1,892 liters/min. at 7.3 kg/cm 2 (500 gpm at 100 psig). Nozzles are to be adjustable from straight stream to full fog and to have a nozzle diameter of at least 12 mm (0.5 in.). Monitors and nozzles are to be of corrosion-resistant materials, and/or be protected with a suitable coating to protect the equipment from the offshore environment. All nozzles are to incorporate means for a shut-off.
       2.Water spraying systems for Process Equipment
            1.A fixed water spray system is to be installed for the process equipment. The intent of the water spray system is to keep the process equipment cool and reduce the risk of escalation of a fire. Water spray systems are to be capable of being actuated both automatically by a fire detection system and manually. Installations are generally to be in accordance with NFPA Standard 15, or other equivalent standard such as API Publication 2030. Deluge isolation valves are to be located in a safe area and outside the fire zone they protect.
       3.Dry Chemical Solutions
            1.For production facilities with no liquid hydrocarbon storage capabilities and limited hydrocarbon liquid retention in processing equipment, dry chemical hose reel units may be used for fire fighting in lieu of firewater station required by 4-8/5.1.3 above. Design of the dry chemical systems is to be in accordance with NFPA Standard 17.
       4.Fixed Fire Extinguishing Solutions
            1.A fixed fire fighting system complying with 4-8/5.5.1, 4-8/5.5.2 or 4-8/5.5.3 is to be provided in each enclosed space and enclosed skid module containing the following equipment:
                1.Internal combustion machinery, including diesel and gas engines, having a total power output of not less than 750 kW (1000 hp)
                2.Oil- or gas-fired boilers and other processes such as incinerators and inert gas generators
                3.If a fixed foam system is to be used for the methanol pump room and methanol tank space, the type of foam selected is to be suitable for use with methane (alcohol-resistant foams).
       5.Gas Smothering Systems
            1.Smothering medium storage location is to be outside of protected space. If gas bottles are kept in an enclosed compartment, the storage space is not to be used for purposes other than storing the bottles. The storage space is also to be situated in a safe and readily accessible position, and be effectively ventilated by a ventilation system independent of other spaces, including the protected space.
            2.Automatic release of fire-extinguishing medium for total flooding systems is not permitted. Two separate controls are to be provided for releasing the fire-extinguishing medium into a protected space and to ensure the activities of the alarm. One control is to be used to discharge the gas from its storage containers. A second control is to be used for opening the valve of the piping, which conveys the gas into the protected space. This requirement is not applicable if the system is provided for a single space and the protected space is relatively small (under 170 m 3 or 6,000 ft 3 ). Controls are to be grouped together to provide complete actuation of the system from their location. The number of release stations is to be limited to as few as possible, typically two, one at the gas storage location and another outside of the protected space. For the one outside of the protected space, it is to be located in proximity and along the main escape route of the space.
            3.Means are to be provided for automatically giving audible warning of the release of fire-extinguishing gas into any space to which personnel normally have access. The alarm is to operate for at least a 20-second period before the gas is released. Alarms may be pneumatically (by the extinguishing medium or by air) or electrically operated. If electrically operated, the alarms are to be supplied with power from the main and an emergency source of electrical power. If pneumatically operated by air, the air supply is to be dry and clean and the supply reservoir is to be atomically kept charged at all times, and is to be fitted with a low-pressure alarm. The air supply may be taken from the starting air receivers. Any stop valve fitted in the air supply line is to be locked or sealed in the open position. Any electrical components associated with the pneumatic system are to be powered from the main and an emergency source of electrical power.
            4.In addition to the above general requirements, the design philosophy of CO 2 fire extinguishing systems is to be in compliance with a single standard/code (i.e., Chapter II-2, Regulations 5 of SOLAS 1974 and Amendments, NFPA 12, or other recognized fire code). Once a standard is chosen for a design basis, the standard is to be used throughout the design, and criteria from other standards may not be used.
            5.Halon is not permitted in new installations. Halon alternative systems are to meet IMO MSC Circ. 848 and general requirements above. Halon alternative agents are to be accepted by the governmental authorities.
            6.Fixed High Expansion Foam Systems
                1.Fixed high expansion foam systems are to be in accordance with Chapter II-2, Regulation 9 of SOLAS 1974 and Amendments or other recognized fire code such as NFPA 11A. Note reference is made to the IMO MSC/Circular 670. 5.5.2
            7.Fixed Low Expansion Foam Systems
                1.Fixed low expansion foam systems may be installed in machinery spaces in addition to the required fixed fire extinguishing system. Fixed low expansion foam systems are be in accordance with Chapter II-2, Regulation 8 of SOLAS 1974 and Amendments or other recognized fire code such as NFPA 11. Note reference is made to the IMO MSC/Circular 582.
       6.Fire Extinguishers
            1.Portable and Semi-portable Extinguishers
 
 

For additional information, please contact :
Atlantis2@mit.edu

©2001 Altantis II Project

Back to Health Section