![](/12.000/www/m2005/a2/finalwebsite/images/transparent.gif) |
Atlantis II Power Requirements and Safety Section
In order to keep the crew of Atlantis
II and the related vehicles safe, many safety regulations must be followed.
These are split into regulations for Main Power and Emergency Power.
Main Power Regulations:
- Two main generators, each of which is to be capable of maintaining the operation of essential equipment on
the platform.
- Both positive and negative conductors from the main and auxiliary power sources are not to pass through the same
penetrator or connection in a pressure boundary and are to be spaced sufficiently to prevent damaging currents.
- All power leads passing through a pressure boundary are to be adequately protected by circuit breakers or fuses
against overload and short circuit.
- The circuit breakers or fuses are to be located on the power source side of the pressure boundary and are to
have the ability to open the circuit quickly to prevent damage to the watertight integrity of the electrical
penetration. Tests may be required to demonstrate the ability of the device to perform as mentioned above.
- Cables and wiring of circuits supplied by different voltages and by the main and emergency circuits are
to be effectively separated from each other.
- Electric plugs, sockets and receptacles are to be of a type which prevent improper inter-connections of the various systems and are to be provided with a means of securing after connection is made.
- The use of a color coding for the various systems is recommended.
- Intrinsically safe wiring is to be separated from non-intrinsically safe wiring by at least 50 mm (2 in) and in accordance with the equipment manufacturer s recommendations. Other suitable standards may be acceptable.
- Propulsion motors inside a pressure boundary of submersible units (i.e. Not subject to pressure) are to be suitable for marine atmosphere, anticipated operating temperatures and shock loading.
- Propulsion motors subject to operational pressure, are to be designed with due considerations to the consequences of
environmental corrosion and pressure, temperature and shock loading. Test data or satisfactory service experience
demonstrating adequacy for intended service are to be used to substantiate the design. When pressure compensators
are used, they are to be supported by complete design and detail plans and calculations. When the adequacy of
pressure compensators is predicated on the complete removal of air inside the housing, the contemplated air purging
procedure is to be included in the operations manual.
Emergency Power Regulations:
- An emergency source of power for systems vital to safety, firefighting and
protection of personnel, is to be provided to supply the services as listed
herein. Provision for emergency power supply less than those listed herein
will be considered, provided adequate technical justification is submitted.
- An emergency source of power may be supplied by an emergency generator or
batteries and must be available in not more than 45 seconds after interruption
of main power.
- If batteries are used and these batteries use cell top terminal potting
they are to possess good dielectric properties and are not to absorb electrolyte,
oil or water at design operating pressures. A dry insulation resistance measurement
is to be made by means of a 500-volt DC insulation resistance test instrument
(megger) between the leads and the insulated casing and is to show a reading
of at least 50 megohms.
- There must be sufficient life support capabilities for twice the time required
to reach the surface.
- A two-way sound-powered communication system is to be provided for each
compartment. The system is to provide communication capability between the
occupants and the outside monitor in the dive control station.
- Speech unscramblers are to be provided when mixed gas is used.
- Any non-sound-powered communication systems are to be supplied by two independent
sources of power.
- The emergency power supply must be able to supply sufficient power for:
- Emergency internal lighting
- Communications equipment
- Life support systems
- Environmental monitoring equipment
- Essential control systems
- Other equipment necessary to sustain life
For additional information, please contact :
Atlantis2@mit.edu
©2001 Altantis II Project
Back to Health Section
|